CNHK large three phase oil immersed transformer for project supply. The published range is above 2000kVA and up to 31500kVA, with voltage up to 38.5kV. Review the conservator, winding, cooling and tap-changer arrangement against the electrical specification.
Select the configuration against your project specification and model-specific data.
PRODUCT OVERVIEW
This large three phase oil immersed transformer is described for power-network connections between different voltage levels. Its construction uses an oil conservator, with off-load or on-load tap-changing options. Winding material, terminals, tank and accessories are selected around the project specification and approved drawings.
The source provides construction details and a broad rating range but no numerical performance table. Losses, impedance, dimensions, mass and the final voltage ratio require selected-design documents. Options described in the text are not universal inclusions.
Large Three Phase Oil immersed power transformers arecustom-built pieces of equipment that are crucial links tothe bulk transmission grid. Usually, they link a generator-transmission line and/or linking lines of different voltages.
CNHK’s Large Three Phase Oil immersed power transformer aremanufactured and tested in accordance the IEC60076
The transformers are of the breathing, conventional type provided with an oil conservator.
Two types of transformers are manufactured:
Transformers with off-load tap changer
Transformers with on-load tap changer
The three legged bolt-less core is constructed of grain oriented steel laminations. The joints between the leg and yokeare mitred at 45° and interleaved. The cross section of the leg is circular.
The material of the windings is either copper or aluminum. The windings are made of paper insulated rectangular wire inthe form of multilayer, disc or helical windings. Transformers provided with on-load tap-changer usually have a separate tap winding.
The transformers are normally equipped with a 5-position off load tap-changer on the High Voltage side, with its handle located on the cover. When changing the tap position the transformer has to be un-energized. Position 1 of the tap-changer (+ position) corresponds with the highest ratio, which gives the lowest voltage on the Low Voltage side. Position5 of the tap-changer (- position) corresponds with the lowest ratio which consequently gives the highest voltage on the Low Voltage side.
The on-load tap-changer is mounted on the cover of the main transformer tank. The tap changer works as a selectorswitch combining the features of a diverter switch and a tap selector. The selector switch is located in a separate oilcompartment which is connected to its own conservator. The selector switch is of the high-speed spring operated typewith resistive transition impedances. The tap-changer is equipped with a protective relay. The selector switch can belifted for inspection and the oil in the compartment can be changed separately. The on-load tap -changer is providedwith a motor drive mechanism for remote and local control. Normally the motor drive is three-phase and the controland the heating circuits are for single phase AC supply. When re-quested, DC circuits can be supplied.
The mineral oil used in the transformers complies with IEC 296 and several national standards. The oil slows down the ageing process.
The transformer tank is usually of the rigid type provided with removable radiators connected to the tank by means of ashut-off valve. On request, the tank can be made vacuum proof.
Transformers up to 5 MVA can be supplied with a compact tank with corrugated cooling fins.
Painting and surface treatment Prior to the painting of the tank, the cover and oil conservator are sandblasted. External surfaces are painted immediately after pre-treatment with a two-pack epoxy primer coat.
Corrugated tanks are flow painted with alkyd primer and acryic finish to a total thickness of 80 um. The conservator and the bottom part of the tank are painted internally.
The transformers are fitted with the following
-Bushings
– Oil conservator with oil level indicator
-Filling and drain valves
-Oil sampling device
-Earthing terminals
– Lifting lugs
-Jacking pads (radiator tanks)
-Rating plate
-Silica-gel breather
-Buchholz relay
-Top oil thermometer
Additional accessories can be fitted in accordance with the customer’s specifications.
Drying and vacuum treatment takes place in a special oven, where the windings are heated electrically while simultaneously the air is evacuated from the oven, reaching an absolute pressure of 1 mbar. The transformer is filled with oil while it is still under vacuum. In this way moisture and gases are effectively remo ved from the windings and oil.
The bushings are of a solid porcelain type and located on the cover. Bushing insulators canbushings comply with IEC 137. be changed without opening the transformer. The
The terminals can be provided with an air insulatedenclosure. The enclosure can be on the primary and/or onthe secondary side and may be constructed for cable orbus duct connection. Alternatively the transformers can be provided with plug-in bushings.
SELECTION GUIDE
Send the required capacity, primary and secondary voltage, frequency, vector group and impedance. Include the network connection and duty so a project-specific data sheet can be prepared.
Specify whether the project needs off-load or on-load tap changing. For an on-load arrangement, include the control supply, local or remote operation and monitoring requirements for technical review.
Provide the installation layout, required tank arrangement and cable or bus-duct interface. The source describes radiator tanks, corrugated tank options and alternative terminals; agree the selected construction in the outline drawing.
Identify protection and monitoring signals, inspection requirements and applicable project standards. Request the agreed losses, dimensions, mass, test records and packing information before technical approval.
MANUFACTURING AND PROJECT EXPERIENCE
Huanghua Group manufactures power transmission and distribution equipment under the CNHK brand. Its published company resources include transformer winding, coil processing and a transformer drying oven. Project support covers selection, drawings, documentation, inspection arrangements and after-sales coordination.

Company transformer winding workshop shown in About Us.

Company coil processing equipment shown in About Us.

Company transformer drying oven shown in About Us.
Company resources and project references do not establish a test certificate for the selected equipment model.
Huanghua Group’s Greece PV Substation Project describes substation and distribution equipment, coordinated protection and site documentation. Review it as a company project reference; the published case does not identify the selected equipment model.
PROJECT SUPPORT
Share the electrical requirements, selected configuration and destination standard. Huanghua Group coordinates technical questions, drawings, document requirements, inspection arrangements and after-sales follow-up against the confirmed product and order scope.
CNHK’s published OEM and ODM programme covers distribution transformers and power distribution equipment. Discuss equipment configuration, integration, labels, packing and project documents. Confirm the equipment-specific OEM scope, branding and customization requests before they become part of the order.
The document package follows the selected configuration, destination requirements and confirmed order.
Review the oil-immersed range, then request the selected design’s electrical data and installation drawing.
TECHNICAL FAQ
The large range describes conservator construction and off-load or on-load tap-changing options. The separately published medium range includes different tank and rating information. Compare the actual project rating and installation requirements rather than treating these pages as one specification.
Oil-immersed transformer rangeThe original summary states above 2000kVA and up to 31500kVA, with voltage up to 38.5kV. These are range limits, not a complete selected-design rating. Provide the actual electrical duty for the quotation.
No. It describes construction, windings, tap changers, tank and accessories without a numerical performance table. Request losses, impedance, dimensions and mass for the selected design; another product’s table is not a substitute.
The source describes transformers with off-load tap changers and transformers with on-load tap changers. The selected arrangement, tap range, control supply and accessory scope need to be stated in the technical agreement.
The original text describes copper or aluminium windings and several terminal or enclosure options. Send the required winding material, cable or bus-duct interface and drawings so the applicable arrangement can be reviewed.
Provide capacity, voltage ratio, frequency, vector group, impedance, tap-changing requirements, cooling and site conditions. Add layout, monitoring signals, quantity, destination and the required document and inspection package.
Send your electrical configuration, drawings, quantity and destination. Our team will review the requirements and the information needed for a quotation.