KYN61-40.5(Z) Metal-Clad AC Enclosed Switchgear, Withdrawable Type

The KYN61-40.5(Z) metal-clad AC enclosed withdrawable switchgear ("switchgear") is Huanghua Group's next-generation medium-voltage assembly for 40.5 kV power transmission and distribution systems. Rated voltage 40.5 kV, rated current up to 2,000 A (2,500 A on request), rated short-circuit breaking current 20 / 25 / 31.5 kA, designed and type-tested to IEC 62271-200.
Send Inquiry

 Product Overview

The KYN61-40.5(Z) metal-clad AC enclosed withdrawable switchgear (“switchgear”) is Huanghua Group’s next-generation medium-voltage assembly for 40.5 kV power transmission and distribution systems. Rated voltage 40.5 kV, rated current up to 2,000 A (2,500 A on request), rated short-circuit breaking current 20 / 25 / 31.5 kA, designed and type-tested to IEC 62271-200. Its armoured, four-compartment, centrally-mounted withdrawable truck design is widely used in power plants, substations, industrial plants and renewable energy stations for power receiving and distribution, providing control, protection and measurement.

Suitable for power receiving, distribution, and the control and protection of motors, transformers and capacitor banks in 40.5 kV systems of power plants, substations, industrial and mining enterprises, rail transit, and renewable (wind / PV / BESS) step-up substations.

Type Designation

image.png

 Key Highlights

Highlight  Description 
IEC-Compliant Metal-Clad Design Fully armoured with four segregated compartments (VCB / busbar / cable / instrument), separated by metallic partitions with pressure-relief ducts, meeting IEC 62271-200 for metal-enclosed switchgear.
Reliable Vacuum Interruption Fitted with the ZN85-40.5 vacuum circuit breaker: mechanical endurance 10,000 operations, opening time ≤0.07 s, spring-mechanism closing time ≤0.15 s, operating sequence O-0.3 s-CO-180 s-CO.
Five-Prevention & IEC Interlocks Five-prevention interlocking (mis-operation, on-load racking, earthing on live circuit, energising with earthing switch closed, access to live compartment) plus all mandatory interlocks of IEC 62271-200.
Generous Creepage & Insulation Margin Phase-to-phase / phase-to-earth creepage ≥720 mm (pollution degree III), 95 kV / 1 min power-frequency withstand, 185 kV lightning impulse withstand, 2,000 V / 1 min on auxiliary and control circuits.
Three-Position Truck, Easy Maintenance VCB truck offers Connected – Test – Disconnected positions, front-operated racking in/out, fully interchangeable trucks of the same rating; maintenance without de-energising adjacent circuits.
Comprehensive Schemes & Customisation More than 24 single-line schemes (001–024+) covering overhead and cable in/outgoing feeders, left/right bus-tie, PT and metering; customised high-altitude, low-temperature (-25 to +45 °C), higher IP and internal-arc (IAC A-FLR) designs available.

Product Features

Feature  Detailed Description 
Armoured Withdrawable Architecture Enclosures are built from CNC-processed aluminium-zinc coated sheet or quality steel plate, assembled with bolts/rivets for high strength, corrosion resistance and dimensional stability; the circuit breaker is a centrally-mounted withdrawable truck.
Four Segregated Compartments VCB, busbar, cable and instrument (LV) compartments are independent, separated by metallic partitions with dedicated pressure-relief ducts, confining any internal arc to a single compartment.
VCB & Operating Mechanism Equipped with the ZN85-40.5 (VS1 series) vacuum circuit breaker with either electromagnetic or spring operating mechanism, electrical and manual emergency operation; mechanical endurance 10,000 operations.
Five-Prevention Mechanical Interlock Mandatory mechanical interlocks and key-exchange procedures between truck, circuit breaker, earthing switch and door eliminate the five categories of mis-operation.
High-Creepage Insulation System Tin-plated electrolytic copper busbars on SMC/DMC insulators and epoxy post insulators, phase-to-phase / phase-to-earth creepage ≥720 mm, suitable for pollution degree III.
Earthing Switch & Earthing System The cable compartment earthing switch provides both maintenance earthing and fault-making capability; the frame PE bus is continuous and bonded to the substation earth grid.
Secondary & Intelligent Interface The instrument compartment accommodates numerical protection relays, energy meters, live-line indicators and SCADA interfaces; secondary wiring runs in dedicated ducts with clear marking for easy commissioning.
IP Rating & Internal Arc Enclosure degree of protection IP3X, IP2X with compartment door open; higher IP ratings and internal-arc classification to IEC 62271-200 Annex AA (IAC A-FLR, 1 s) available on request.
Installation & Maintenance Convenience Front operation and maintenance, generous bottom cable-entry space, well-laid-out CTs, surge arresters and live-line indicators; standard foundation drawings simplify on-site lineup.
Scheme Flexibility & Customisation Selectable schemes 001–024+ for incomer, outgoing, bus-tie, tie, PT/metering and capacitor circuits; special versions for low temperature, high altitude, salt mist and higher ingress protection.

Technical Parameters

1.Switchgear Panel Parameters

Parameter Unit Data Standard & Remark
Rated voltage kV 40.5 IEC 62271-200;Um = 36kV(IEC 62271-1)
Rated frequency Hz 50( 60 Hz customised) GB/T 11022;50/60Hz
Rated current of main busbar A 1250,1600,2000,(2500) values in brackets: customised
Rated current of matched VCB A 1250,1600,2000,(2500) higher ratings on request
1 min power-frequency withstand voltage (rms) kV 95 type-tested value
Lightning impulse withstand voltage (peak) kV 185 BIL 185kV, insulation coordination with 40.5kV transformer
Power-frequency withstand voltage of auxiliary & control circuits V / 1 min 2000 Secondary circuit insulation level
Rated short-circuit breaking current kA 20 / 25 / 31.5 IEC 62271-100(VCB)
Rated short-time withstand current / duration kA / 4 s 20 / 25 / 31.5 Icw 4s
Rated peak withstand current kA 50 / 63 / 80* *80kA subject to configuration
Rated short-circuit making current kA 50 / 63 / 80* *80kA subject to configuration
Rated voltage of control circuit V DC 110 / 220;AC 110 / 220 as specified in order
Degree of protection — switchgear enclosure — IP3X IEC 60529; higher IP optional
Degree of protection — compartments (door open) — IP2X IEC 60529
Creepage distance (phase-phase / phase-earth) mm ≥720  pollution degree III
Internal arc classification — IAC A-FLR(on request) IEC 62271-200  31.5kA 1s
Compartmentalisation — Four compartments: Circuit breaker/Busbar/Cable/Instrumentation 4 compartments: VCB / busbar / cable / instrument
Interlocking — Five-proof mechanical interlock + IEC forced interlock Five-prevention (GB 3906) + IEC mandatory interlocks
Enclosure material & construction — Aluminized zinc plate / high-quality steel plate assembly Al-Zn coated sheet or steel plate, CNC-assembled
Typical panel width mm 1400 (Standard) / 1680 (KYN61A Wide Type) subject to outline drawing
Typical panel depth mm 2800 subject to outline drawing
Cable / busbar entry — Overhead incoming/outgoing lines / Cable incoming/outgoing lines / Busbar connections Overhead or cable in/outgoing, bus-tie

2.Vacuum Circuit Breaker Parameters (ZN85-40.5)

Parameter  Unit Data
Rated voltage kV 40.5
Rated current A 1250,1600,2000,(2500)
Rated frequency Hz 50
Rated short-circuit breaking current kA 20 / 25 / 31.5
Rated short-circuit making current kA 50 / 63 / 80
Rated peak withstand current kA 50 / 63 / 80
Rated short-time withstand current / duration kA / 4 s 20 / 25 / 31.5
1 min power-frequency withstand voltage (rms) kV 95
Lightning impulse withstand voltage kV 185
Power-frequency withstand voltage of auxiliary & control circuits V / 1 min 2000
Mechanical life (endurance) operations 10000
Closing time — electromagnetic mechanism s ≤0.2
Closing time — spring mechanism s ≤0.15
Breaking (opening) time s ≤0.07
Rated operating sequence — O-0.3s-CO-180s-CO
Truck positions — Connected / Test / Disconnected

3.Normal Service Conditions

Item (EN)  Unit Data
Ambient air temperature ℃ -15 ~ +40
Altitude m ≤1000
Relative humidity — daily average % ≤95
Relative humidity — monthly average % ≤90
Water vapour pressure — daily average kPa ≤2.2
Water vapour pressure — monthly average kPa ≤1.8
Earthquake intensity — magnitude 8
Installation location — Indoor
Special environments — Customised

4.Applicable Standards & Testing

Standard / Test Code Scope Remark
AC metal-enclosed switchgear and controlgear IEC 62271-200 Cabinet design, type testing and mandatory interlocking  main product standard
High-voltage alternating-current circuit breakers IEC 62271-100 ZN85-40.5 Vacuum Circuit Breaker Breaking and closing test basis
AC metal-enclosed switchgear 3.6–40.5 kV GB 3906 Five-prevention interlocking and domestic engineering acceptance for domestic projects
Common specifications for HV switchgear GB/T 11022 Ratings and General Technical Requirements Corresponding to IEC 62271-1
Degrees of protection provided by enclosures IEC 60529 (IP code) IP3X / IP2X Authentication Dustproof probe ϕ1mm test
Power transformers (matching equipment) IEC 60076-1 Insulation coordination with 40.5kV transformer transformer side
Low-voltage switchgear assemblies (matching) IEC 61439-2 When supplied as a complete set with low-voltage switchgear matching equipment

5.Type Tests & Routine Tests

Test Item  Type Test Condition Remark
Dielectric test  Type Power-frequency 95 kV / 1 min; lightning impulse 185 kV (peak) Applied to earth, between phases and across the open break as required by the standard
Short-circuit making and breaking test  Type 31.5 kA (40 kA on request) Per IEC 62271-100, carried out with the rated operating sequence O-0.3 s-CO-180 s-CO
Short-time and peak withstand current test  Type 31.5 kA / 4 s (busbars, branch connections and joints) Verifies dynamic (peak) and thermal withstand of main and earthing circuits
Temperature-rise test  Type Full-load cyclic duty; temperature rise at contacts and joints ≤65 K Confirms continuous current-carrying capability with stable contact resistance
Mechanical endurance (mechanical operation) test  Type VCB 10,000 operations; withdrawable truck 1,000 operations Mechanical endurance class C2 (M2 / E2 subject to order confirmation)
Internal arc test Type (on request) IAC A-FLR, 31.5 kA / 1 s IEC 62271-200 Annex AA; assesses accessibility type for front, lateral and rear
Verification of the degree of protection (IP code) Type IP3X (φ1.0 mm test probe, no ingress) IEC 60529; IP2X with the compartment door open
Power-frequency voltage withstand test (each cubicle) Routine 85 kV / 1 min (to earth) Performed on every cubicle before delivery
Measurement of the resistance of main and earthing circuits Routine DC voltage-drop method; measured value not exceeding the design limit Performed on every cubicle to verify joints and contacts
Mechanical operating and timing (travel) tests Routine Opening / closing times, pole synchronism ≤2 ms; travel and clearance Performed on every cubicle; characteristic curves retained
Functional check of interlocks and five-prevention Routine Interlocks between truck three positions, circuit breaker, earthing switch and door Includes IEC 62271-200 mandatory interlocks and GB 3906 five-prevention
Inspection of auxiliary wiring, appearance and tightening torque Routine Wiring correctness, ferrule marking, tightening torque and overall finish Performed on every cubicle; critical torque points marked for traceability

Engineering & Design Excellence

1 Gas Medium & Dielectric Design (the core differentiator)

Unlike SF₆ (εᵣ ≈ 1.002, excellent arc-quenching), dry air / N₂ has lower relative permittivity and arc-quenching capability, requiring compensated design:

Slightly elevated filling pressure (1.4–1.5 bar abs vs. 1.3–1.4 for SF₆) to maintain same Pf / BIL coordination

Enhanced creepage design: creepage ≥ 720 mm (pollution degree III), silicone-based coating on insulators optional for coastal/high-humidity

VCB as primary breaking element (not LBS-alone for feeder duties): dry air/N₂ has weaker arc-quenching than SF₆, so V-module (VCB 31.5 kA) is recommended for transformer/fault protection rather than relying on LBS+fuse alone in high-fault-current sites

Gas composition: dry air (filtered, dew point < –40°C) or N₂ blend — GWP < 1, zero SF₆, zero PFC

Professional nuance: IEC 62271-214 explicitly acknowledges that alternative gases (dry air, N₂, blends) require higher design pressure and/or enhanced contact/insulator geometry vs. SF₆-filled counterparts at same Ur. Huanghua’s 40.5kV eco-gas inherits the 12kV XIHARI-certified pressure-boundary welding + helium-leak workflow, then scales creepage, BIL coordination, and VCB rating per 40.5kV.

2 Welded Stainless-Steel Gas Tank (platform-pedigree shared with 12kV eco-gas & 24kV SF₆ RMU)

304L stainless, laser-welded longitudinal + circumferential seams — same regime as XIHARI-certified 12kV eco-gas

Helium leak test per tank (≤ 0.5% / yr equivalent) — critical because dry air/N₂ leakage = insulation level drop (no SF₆ self-healing effect)

Pressure Relief: Non-rupturable diaphragm, vented to cabinet top

Gas Density Monitor: Temperature-compensated, alarm + lockout at 0.9 / 0.8 bar abs — dry-air/N₂ density directly correlates to dielectric strength, so density monitoring is even more critical than SF₆

3 Switch & Breaking (VCB-prominent architecture)

Element Application Breaking Capacity
Load Break Switch (LBS) C-module (ring in/out), De (earthing) Load make-break; fault withstand via fuse coordination (F-module)
Vacuum Circuit Breaker (VCB) V-module 31.5 kA / 25 kA breaking, C2 class (10,000 ops) — recommended primary for transformer protection in eco-gas version

Three-position LBS: Close – Open – Earth, single handle + mechanical interlock
VCB: VS1 domestic / VD4-compatible, spring mechanism

4 Busbar, Cable & Earthing (architecture inherited from RMU platform)

SF₆-free tank internals: busbars, LBS, VCB, fuse-carrier, ES — all dry-air/N₂ insulated

Extensible via plug-in silver-plated finger contacts, bellows-sealed, field-expandable without de-gassing adjacent bays

Bottom cable entry, CT/PT built-in, De-module earthing per bay

5 Enclosure & Environmental

Outer cabinet: galvanized steel, powder-coated RAL 7035

IP54 outer cabinet on request (coastal / dusty)

Anti-condensation heater (cabinet compartment)

Operating temperature: –40°C to +70°C (tank); cabinet electronics –25°C to +55°C (heater-assisted)