HKYBW-40.5 Prefabricated Compact Substation
Product Overview
Huanghua Group’s HKYBW-40.5 and HKYBW-12 series prefabricated compact substations are factory-integrated power distribution units that consolidate medium-voltage switchgear, power distribution transformer, and low-voltage switchgear into a single outdoor-rated enclosure. Engineered as a turnkey alternative to conventional civil-engineered substations, the compact substation delivers identical capacity in just 1/10 to 1/5 of the footprint , drastically reducing design workload, construction volume, and total project cost.
Each unit is pre-assembled, pre-wired, and routine-tested at our factory, then shipped as a single lift-and-place module — eliminating on-site civil works and compressing commissioning from months to days. The HKYBW series is fully compliant with IEC 62271-202 (AC prefabricated substations up to 52kV) , IEC 60076 (power transformers), and IEC 61439 (low-voltage switchgear assemblies), qualifying it for EU tenders, utility distribution networks, and global EPC projects.
With rated voltages up to 40.5kV and capacities from 100 to 2500 kVA , the HKYBW series serves ring network distribution systems, dual-power radial end distribution, urban and rural grid expansion, renewable integration, industrial parks, and temporary/mobile power scenarios.
General Specifications
| Parameter | Specification |
| Product Model | HKYBW-40.5 Series (up to 40.5kV) / HKYBW-12 Series (up to 12kV) |
| Product Type | Prefabricated Compact Substation (Euro-Style Box-Type) |
| Rated Power Range | 100 – 2500 kVA |
| Rated Frequency | 50Hz / 60Hz (optional) |
| Max. Rated Voltage | 12kV / 24kV / 40.5kV (3 selectable classes) |
| LV Rated Voltage | 0.4 kV (400/230V) |
| Compartment Configuration | 3 independent compartments: MV switchgear / Transformer / LV switchgear |
| Structural Features | Anti-misoperation interlocking, lifting lugs for integrated transport, weather-resistant housing, reduced dimensions |
| Ventilation | Natural ventilation standard; forced ventilation optional with automatic temperature control |
| Surface Treatment | Anti-corrosion treatment, electrostatic powder coating (custom RAL on request) |
| Applicable Standards | IEC 62271-1 / IEC 62271-200 / IEC 62271-202 / IEC 60076 / IEC 61439 / IEC TR 62271-208 / IEC 60529 / IEC 62262 / IEC 60721 |
| Compliance | CE · ISO 9001 |
| Third-Party Cert. | TÜV Rheinland (type test report available) · KEMA/DEKRA (on request) |
| Footprint Advantage | 1/10 – 1/5 of conventional civil substation |
Technical Data by Voltage Class
Up to 12kV Class
| Description | Unit | HV | Transformer | LV |
| Max. Rated Voltage | kV | 12 | 12/0.4 | 0.4 |
| Max. Rated Current | A | 630 | — | 100 – 3150 |
| Power Frequency Withstand (1 min) | kV | 42 | 42 | 3 |
| Lightning Impulse Withstand | kV | 95 | 95 | — |
| Short-time Withstand Current | kA | 25 | — | 30 – 80 |
| Peak Withstand Current | kA | 62.5 | — | 63 – 176 |
| Rated Breaking Load Current | A | 630 | — | — |
| Protection Degree | — | IP65 | IP54 | IP23 |
| Noise Level | dB | — | Oil 55 / Dry 65 | — |
| No. of Circuits | — | 1 – 6 | — | 4 – 30 |
| Max. Reactive Power Compensation (LV) | kVAR | — | — | 30% of rated power |
Up to 24kV Class
| Description | Unit | HV | Transformer | LV |
| Max. Rated Voltage | kV | 24 | 24/0.4 | 0.4 |
| Max. Rated Current | A | 630 | — | 100 – 3150 |
| Power Frequency Withstand (1 min) | kV | 50 | 50 | 3 |
| Lightning Impulse Withstand | kV | 125 | 125 | — |
| Short-time Withstand Current | kA | 25 | — | 30 – 80 |
| Peak Withstand Current | kA | 62.5 | — | 63 – 176 |
| Rated Breaking Load Current | A | 630 | — | — |
| Protection Degree | — | IP65 | IP54 | IP23 |
| Noise Level | dB | — | Oil 55 / Dry 65 | — |
| No. of Circuits | — | 1 – 6 | — | 4 – 30 |
| Max. Reactive Power Compensation (LV) | kVAR | — | — | 30% of rated power |
Up to 40.5kV Class
| Description | Unit | HV | Transformer | LV |
| Max. Rated Voltage | kV | 40.5 | 40.5/0.4 | 0.4 |
| Max. Rated Current | A | 630 | — | Up to 3150 |
| Power Frequency Withstand (1 min) | kV | 95 | 95 | 3 / 2.5 |
| Lightning Impulse Withstand | kV | 250 | 250 | — |
| Short-time Withstand Current | kA | 25 | — | 30 – 80 |
| Peak Withstand Current | kA | 62.5 | — | 63 – 176 |
| Rated Breaking Load Current | A | 630 | — | — |
| Protection Degree | — | IP65 | IP54 | IP23 |
| Noise Level | dB | — | Oil 55 / Dry 65 | — |
| No. of Circuits | — | 1 – 6 | — | 4 – 30 |
| Max. Reactive Power Compensation (LV) | kVAR | — | — | 30% of rated power |
All data above sourced from Huanghua HKYBW series technical datasheet .
Integrated Functional Modules
1 MV Switchgear Compartment
The high-voltage compartment integrates all primary and protection equipment:
MV Switchgear: Vacuum circuit breaker as standard
Relay Protection: Comprehensive protection against transformer faults, through-faults, and overloads
Current Transformers: For measurement and protection
Optional RMU: Ring Main Unit configuration available
Optional LBS Protection: Load Break Switch protection
Optional CTs/PTs: For metering and synchronization
Basic Impulse Level: Adjustable on request
Protection Degree: IP65
2 Transformer Compartment
The core step-up/step-down unit, engineered for reliability and environmental resilience:
Winding Material: Copper winding standard; aluminum winding optional
Transformer Types: Oil-immersed or dry-type (optional per application)
Core & Coil Losses: Various loss solutions available (lower losses on request)
Short-circuit Withstand: External short circuits withstanding ≥ 0.5 seconds
Animal/Bird/Vermin Protection: Sealed design minimizes accidental short-circuit risk
Options: Non-standard HV taps, special impedance, special noise levels
Noise Level: Oil type ≤ 55 dB; Dry type ≤ 65 dB
Protection Degree: IP54
3 LV Switchgear Compartment
A full IEC 61439-compliant low-voltage distribution assembly:
Provision for LV Panel: Compatible with Huanghua MNS / GCS / GCK platforms
Incomer: ACB and MCCB provisions
Current Transformers: For instrument operation
Power Distribution Function: Full provision for downstream distribution
Optional Reactive Power Compensation: Up to 30% of rated power
Optional Energy Metering: Energy metering and measurement function
Optional LV Panel Types: Various configurations per customer specification
Protection Degree: IP23 (IP54 available on request)
Circuit Count: 4 – 30 circuits
Structural Design Highlights
1 Three Independent Compartments
Physically segregated MV switchgear, transformer, and LV switchgear compartments ensure safe maintenance access, fire containment, and operational isolation. Each compartment operates under its own optimized protection class (IP65 / IP54 / IP23 respectively).
2 Anti-Misoperation Interlocking
Mechanical and electrical interlocks prevent incorrect operating sequences, protecting personnel and equipment during switching operations.
3 Lift-and-Place Mobility
Integrated lifting lugs allow the entire unit to be transported and positioned as a single module — no disassembly, no on-site civil works. This mobility characteristic makes the HKYBW series ideal for temporary power, emergency restoration, and rapidly deployable infrastructure.
4 Weather-Resistant Housing
Engineered for outdoor installation with anti-corrosion treatment as standard. The enclosure withstands diverse environmental conditions — from coastal salt-spray to desert solar radiation to grassland humidity — making it suitable for beaches, grasslands, deserts, and high-UV regions .
5 Intelligent Thermal Management
Natural ventilation as standard; forced ventilation with automatic temperature control device available. The system activates/deactivates based on setpoint temperature, ensuring optimal thermal performance without manual intervention.
6 Reduced Dimensions & Minimal Footprint
Compact structure occupies only 1/10 to 1/5 of the area required by conventional civil-engineered substations , dramatically reducing land acquisition costs and enabling deployment in space-constrained urban and industrial environments.
7 Aesthetic Integration
Diverse external decoration options allow the substation to harmonize with surrounding architectural and environmental contexts — a critical advantage for urban and commercial deployments.
Engineering Options & Accessories
| Category | Available Options |
| Environmental | Special ambient condition adaptation |
| Transformer | Lower average winding temperature rise; lower losses of core and coil; oil-immersed or dry-type; non-standard HV taps; special impedance; special noise levels |
| MV Side | RMU configuration; LBS protection; CTs & PTs; adjustable basic impulse level |
| LV Side | Reactive power compensation; energy metering & measurement; various LV panel types; APFC panels |
| Protection | Electrostatic shields; internal arc fault classification (IAC) |
| Finish | Special paint finishes; custom RAL color; anti-graffiti coating |
| Standards | Basic impulse level adjustable on request |
Routine & Type Tests
Routine Tests for Each Unit
Visual & dimensional inspection per IEC standards
Wiring continuity & terminal torque verification
Insulation resistance test
Power frequency withstand voltage test (1 min) per voltage class
Lightning impulse withstand voltage test
Functional operation test of circuit breakers, interlocks, and protection relays
Temperature rise verification
As-built schematic vs. actual wiring validation
Type Tests
Dielectric Test: Power-frequency withstand (42kV / 50kV / 95kV per class) and lightning impulse (95kV / 125kV / 250kV per class)
Short-time Withstand (Icw): 25 kA @ 1s on HV side; 30–80 kA on LV side
Peak Withstand (Ip): 62.5 kA on HV side; up to 176 kA on LV side
IP Verification: IP65 (MV) / IP54 (Transformer) / IP23 (LV)
Mechanical Operation: Circuit breaker endurance and interlock sequence
Internal Arc Classification: Available upon request
Transport Simulation: Lifting lug load test
Full type test reports available upon request
Applications
| Sector | Recommended Configuration | Rationale |
| Urban / Rural Grid Expansion | HKYBW-12 / HKYBW-40.5, 100–2500 kVA | 1/10–1/5 footprint vs. civil substation; ring network compatible |
| Ring Network Distribution | HKYBW with RMU option | 1–6 MV circuits, SF₆ (free) RMU or VCB, IEC 62271-202 compliant |
| Dual-Power / Radial End Distribution | HKYBW with VCB + relay protection | Comprehensive transformer fault & overload protection |
| Industrial Plants & Mining | HKYBW-40.5, dry-type option, IP54 transformer compartment | Dust-resistant, anti-corrosion, 62.5 kA peak withstand |
| Renewable Energy (PV / Wind) | HKYBW-24 / HKYBW-40.5, 2500 kVA | Beach/grassland/desert adaptable, pre-assembled for rapid deployment |
| Commercial & Residential Complex | HKYBW-12, oil-immersed, IP65 MV compartment | Aesthetic exterior options, low noise (55 dB oil type) |
| Emergency / Temporary Power | HKYBW series, lift-and-place mobility | Single-module transport, minimal on-site works |
| Coastal / Marine / Chemical | HKYBW with special anti-corrosion coating | C5-grade protection, sealed against salt-spray and vermin |
| Data Center / Mission Critical | HKYBW-40.5, dry-type, internal arc classified | 40.5kV grid connection, IAC available, redundant configurations |